Bussmann series NH Fuse links, bases and gear catalogue CA132063EN - August 2019 www.eaton.com 23 1.2 1.2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Data sheet 10623 NH Fuse links - 400 Va.c. - class gFF Timecurrent characteristics and technical data 400 Va.c. - class gFF - 10 to 100 amps - size 000 Timecurrent characteristics 3UHDUFLQJ7LPH>V@ 3URVSHFWLYHFXUUHQW>$@ ϲϯ ϴϬ ϭϬϬ ϯϱ ϱϬ ϭϬ ϭϲ Ϯϱ Technical data Catalogue numbers with insulated metal gripping lugs Fuse link size Current (amps) Voltage (Va.c.) I²t (Amps² seconds) Watts loss (W) Net weight per fuse (kg) Minimum Prearcing *I1 120 kA at 400 Va.c. 10NHFF000BI-400 000 10 400 44 180 1.7 0.113 16NHFF000BI-400 16 160 600 2.3 25NHFF000BI-400 25 1000 3200 2.3 35NHFF000BI-400 35 2700 8300 2.7 50NHFF000BI-400 50 3100 8800 5.4 50NHFF000BI-400 63 6400 18700 6.5 50NHFF000BI-400 80 12300 32000 8 50NHFF000BI-400 100 24600 59000 9 * I1 is the maximum breaking capacity test at voltage according to IEC 60269-1 and 2 requirements